Technical Specifications: | |
Catalog Number | HW272 01404 |
Size AWG | 14 |
mm2 | 2.1 |
Nominal Diameter (inches) | 0.619 |
Weight (lbs/Mft.) | 262 |
DC Resistance at 25° C (Ohms/1000 ft.) | 2.907 |
AC Resistance at 110°C, 60 Hz (Ohms/1000 ft.) | 3.859 |
Inductive Reactance (Ohms/1000 ft.) | 0.039 |
Voltage Drop at 110°C (Volts/Amp/1000 ft.) | 5.382 |
Opt. Uninsulated Grounding Cond. Size AWG 1 | -- |
Ampacity 110°C | 27 |
Ampacity 100°C | 25 |
Ampacity 95°C | 22 |
Specifications:
Application:
Designed and constructed for the demanding environments of offshore drilling and petroleum facilities located throughout the world.
Conductors:
Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.
Insulation:
Flame Retardant Cross-linked Polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA C22.2 No. 245. Color Code: Black-White-Red-Green. Sizes 1/0 and Larger: Black with Phase ID Imprint.
Jacket:
Black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA C22.2 No. 245 and IEEE 1580.
Armor:
Basket weave wire armor per IEEE 1580 and UL 1309/CSA C22.2 No. 245. Bronze standard. Tinned copper available by request.
Sheath:
A black, arctic grade, flame retardant, oil abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA C22.2 No. 245 and IEEE 1580.
Ratings & Approvals :
Features: