Technical Specifications: | |
Size (AWG or kcmil): | 10 |
No. of Conductors | 3 |
Net Weight: | 300 |
Overall Diameter (Inches): | 0.72 |
Insulation Thickness (Mils): | 30 |
Jacket Thickness (Mils): | 50 |
No. of Strands: | 7 |
Class 1 Div.2 Connector No.: | 424CU03 |
Rain Tight Connector No.: | 416MC03 |
Specifications:
Application:
For use in harsh environments where maximum conductor protection is required. Used for power, control and lighting circuits in a broad range of commercial and industrial pulp and paper, mining, and petroleum applications. Approved for use in wet or dry locations at 90°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 and Class III, Division 1 and 2 hazardous locations. UL approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Aluminum interlocked armor cable is recommended as an economical alternative to wire in conduit systems.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).
Insulation:
Cross-linked polyethylene (XLP) per UL Standard 44 for Type XHHW-2, VW-1 conductors.
Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1569.
Armor:
Aluminum interlocked tape armor per UL Standard 1569. Also available in galvanized steel armor.
Jacket:
Black sunlight-resistant PVC per UL Standard 1569.
Flame Tests:
UL 1581 70,000 BTU/hr flame test
Color Code:
ICEA Method 1, Table E-2
Connectors:
Explosion Proof, Class 1 Division 2: 424CU series – aluminum exterior components, nickel-plated brass interior components
Rain Tight: 416MC series – all nickel-plated brass